Product Overview
The Graphic Annunciator Driver is an interface card that connects the Edwards Intelligent control panel to the display panel of an LED-based graphic annunciator (sold separately). The annunciator card supports 32 LEDs on the graphic panel display (E-FSA250) and 16 on E-FSA64. It includes status LEDs and an internal buzzer. The graphic interface is supplied with snap track mounting. It is attached to a plastic mounting rail that requires two EIA panels. The annunciator communicates with the control panel on the RS-485 data riser. This can be configured for Class A or Class B communication. The annunciator does not provide ground fault isolation. It is a stand-alone unit that can be powered by the control panel or by an approved power supply.
- Five dedicated switch inputs for common controls
- Sixteen programmable switch inputs
- Eleven dedicated LED outputs for power, common controls, system status, and enable controls indicators
- Thirty-two programmable LED outputs for zone or device status indicators
- A buzzer that sounds when the control panel activates an event
General Information
Name : Edwards Signaling GCI Graphic Annunciator Interface , Edwards Signaling
Category : Annunciators
UPC Code : 793017005952
Country of Origin : CN. Country of origin is subject to change.
Specifications
General Information
ADI Part Number : ED-GCI
Brand Name : Edwards Signaling
Manufacturer : Carrier
Manufacturer Part Number : GCI
Product Name : GCI Graphic Annunciator Interface Card
Product Type : Annunciator Module
Technical Information
Device Supported : Control Panel
Environmental Conditions
Maximum Operating Temperature : 120°F (48.9°C)
Maximum Operating Temperature (°F) : 120
Minimum Operating Temperature : 32°F (0°C)
Minimum Operating Temperature (°F) : 32
Physical Characteristics
Color : White
Power Description
Input Voltage : 24V DC
Input Voltage (V DC) : 24
Miscellaneous
Country of Origin : CN
Environmentally Friendly : Yes