Product Overview
The SD500-AIM and SD500-MIM are addressable input modules for use with the Intelliknight fire alarm control panels (FACPs). The SD500-AIM addressable input module mounts to a 4"-square box. The SD500-MIM mini input module fits inside a single gang box. Both input modules are designed to be used with pull stations, water flow switches, and other applications requiring dry contact alarm initiation devices.
These modules are supervised, single input contact monitors. Using an EOL resistor, they monitor for alarm contact closures and for open circuit wiring fault conditions. If a fault occurs in the wiring, the module alerts the FACP. Each addressable input module is programmed with a unique signal line circuit (SLC) loop address.
Features
- Single contact monitor
- SD500-AIM supports Class A (Style D) or Class B (Style B) contact monitor wiring
- SD500-MIM support for Class B (Style B) contact monitor wiring
- Attractive ivory cover plate with the SD500-AIM
- Small and lightweight size allows for flexible mounting options with the SD500-MIM
- DIP switch programmable for fast installation
- Up to 2500 ft wiring distance from either input module to contact
- Use up to 14 gauge wire
- UL listed
General Information
Name : Silent Knight SD500-AIM Addressable Input Module , Silent Knight by Honeywell
Category : Control Panel Modules
UPC Code : 999999530360
Country of Origin : Mexico. Country of origin is subject to change.
Specifications
General Information
ADI Part Number : 9R-SD500AIM
Brand Name : Silent Knight by Honeywell
Manufacturer Part Number : SD500-AIM
Product Model : SD500-AIM
Product Name : SD500-AIM Addressable Input Module
Product Type : Addressable Input Module
Miscellaneous
Country of Origin : MX