The MRP-2001 is a six-zone FACP for single and dual hazard deluge and preaction applications. The MRP-2001 provides reliable fire detection, signaling and protection for commercial, industrial and institutional buildings requiring water-based releasing. The MRP-2001 is compatible with System Sensor's i3 detectors which are conventional smoke detectors that can transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory 'freeze' signal when the ambient temperature falls below the detector rating of approximately 45°F (7.22°C). In addition, the control panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to the FireLite Device Compatibility Document for a complete listing of compatible devices. MRP-2001Features and Benefits 6-zone Style B (Class B) or 6-zone Style D (Class A) with optional modules 4 Programmable Output Circuits Style Y (Class B) or 4 Programmable Output Circuits Style Z (Class A) with optional modules Outputs programmable for Releasing Solenoids Dual hazard operation Adjustable waterflow discharge timer and two soak timers Cross-zone capability Pre-programmed and custom application templates Built-in NAC synchronization for System Sensor, Wheelock, Gentex, Faraday and Amseco devices Built in programmer: Integral 80 character LCD display with backlighting and keypad Annunciator bus supports up to 8 devices, including ANN-80 LCD Remote Annunciator, remote serial or parallel printer gateway, and LED graphic annunciator 7.0 amps total usable current