Product Overview
302 Series Heat Detector (Rate Compensation), 6-125VAC/6-25VDC/125VDC, indoor/outdoor box mounting, 135 F UL rated, -40 F min ambient, 100 F max ceiling, 4 in L x 1 in base diameter. 302-ET-135 Edwards Series 302 heat detectors are suitable for use in indoor and outdoor environments and explosive atmospheres. They are normally-open devices designed to close an electrical circuit upon activation. All models feature rate compensation and are available with either 135°F (57.2°C) or 194°F (90°C) ratings. These self-restoring, hermetically sealed detectors are shock-, corrosion- and tamper-resistant.
FEATURES
- Rate compensation offsets thermal lag
- Self-restoring – no manual reset required
- Explosionproof versions available. Class 1, Groups C and D; Class 2, Groups E, F and G
- Some versions suitable for outdoor applications
- No back box required on some outdoorsuitable versions
- Box mount and surface mount versions
General Information
Name : Edwards Signaling 302-ET-135 All-weather Heat Detector Rate Compensation, Vertical, Box Mount (½" NPT), FM and UL, 135 °F (57.2 °C) , Edwards Signaling
Category : Media Converters
UPC Code : 0793017005341
Country of Origin : US. Country of origin is subject to change.
Specifications
General Information
ADI Part Number : ED-302ET135
Brand Name : Edwards Signaling
Connectivity Technology : Wired
Manufacturer : Carrier
Manufacturer Part Number : 302-ET-135
Product Model : 302-ET-135
Product Name : 302-ET-135 Temperature Sensor
Product Series : 302
Product Type : Temperature Sensor
Technical Information
Temperature Accuracy : 135°F (57.2°C)
Category Specific Attributes
Heat Detector Type : Fixed Temperature|Rate of Rise
Physical Characteristics
Color : White
Form Factor : Box Mount
Power Description
Input Voltage : 120V AC, 125V DC, 25V DC
Input Voltage (V AC) : 120
Input Voltage (V DC) : 125, 25